Saturday, June 11, 2016

Control Valve

Om Swastiastu,

It's been a long time since my last post, and I've received many responses especially about Heat Exchanger through my email, so I would to say thank you for your attention, hopely I can help you with your task or engineering issue, but if I can't do much about it please understand due to my lack experiences.

This time I would like to tell you a story about control valve. Even if control valve looks small in EFD (Engineering Flow Diagram) or P&ID (Piping & Instrumentation Diagram), It holds the continuity duty of your plant. With poor understanding and selection of control valve, you will face difficulty to operate your plant. hereby I describes the calculation methods and the behavior of control valve.

Control Valve is the most common final control element in the process control loop. The control valve manipulates a flowing fluid, such as gas, steam, water, or chemical compounds to compensate for the load disturbance and keep the regulated process variable such as flow, pressure, temperature and liquid level as close as to the desired set point. The control valve is operated by fully or partially opening or closing the flow passage in response to the received signals from the controller.

Control valve assembly typically consists of two main parts which are the valve body and the actuator to provide the motive power to operate the valve.


Cv (Flow Coefficient) Calculation

The sizing of valve requires data from vendors on specific trim. They use a valve flow coefficient (Cv) that depends on the internal dimensions and smoothness of the surface. These coefficients are capacity index based on tests made by manufacturers using air or water at an established pressure difference. The calculation of valve Cv is carried out by using InstruCalc Plus or other vendor software (e.g. FirstVue and ValspeQ). The following section describes the general equations to calculate the valve Cv. The equation of flow coefficient for incompressible flow may be used with caution for non-vaporizing multi-component liquid mixture. The fundamental flow model for incompressible fluids is given as follow.
Where,
      Cv          = Flow Coefficient
      Q            = Actual Volumetric Flowrate, gpm
      FP           = Piping Geometry Factor
      ΔPsizing    = Differential Pressure used for calculation, psia
      SL               = Specific Gavity, 1.0 for water at 150C

This formula establishes the relationship between flowrate, flow coefficient, flow properties, related installation factors and differential pressure. The value of differential pressure used in the formula is the actual differential pressure or the choked differential pressure which one is the least.
The condition where further increase in pressure differential pressure at constant upstream pressure but no longer produce a corresponding increase in flowrate is called choked flow. The differential pressure which this condition occurred is known as choked differential pressure and given by the following equation.
The expression (FLP/FP)reduces to FL when the valve size and adjoining pipe sizes are identical.
Where,
      FLP       = Combined liquid pressure recovery factor and piping geometry factor
      FP         = Piping Geometry Factor
      FL         = Liquid Pressure Recovery Factor (retrieved from manufacturer data)
      P1         = Inlet Pressure, psia
      FF         = Liquid Critical Pressure Ratio Factor
      PV        = Liquid Vapor Pressure, psia

The liquid critical pressure ratio factor is the ratio of apparent vena contracta pressure at choked flow condition to the vapor pressure of the liquid at inlet temperature and can be calculated by the following equation.
Where,
      PV        = Liquid Vapor Pressure, psia
      PC        = Critical Pressure, psia

At very low ratio of differential pressure to absolute inlet pressure (ΔP/P1), compressible fluids behave similarly to incompressible fluid. However, increasing value of ΔP/P1 ­results in compressible effect that require modification to the basic equation with appropriate correction factor. The equation for compressible fluids is for ideal gas or vapor and not intended to use for multiphase stream. The fundamental flow model for compressible fluids is given as follows.
Where,
      Cv       = Flow Coefficient     
      W        = Mass Flowrate, lbm/h
      FP       = Piping Geometry Factor
      P1       = Inlet Pressure, psia
      Y         = Expansion Factor
      xsizing  = Ratio of Differential Pressure to Absolute Inlet Pressure (ΔP/P1
      M        = Molecular Weight, lbm/lbmole
      T         = Inlet Temperature, 0R
      Z         = Compressibility Factor at Inlet Condition

This formula establishes the relationship between flowrate, flow coefficient, flow properties, related installation factors and the pressure drop ratio to inlet pressure. The pressure drop ratio used in this formula is the actual pressure drop ratio or the choked pressure drop ratio which one is the least.
The pressure drop ratio in which flow no longer increases with increased value in pressure drop ratio is the choked pressure drop ratio, as given by the following equation.
The expression xTP reduces to xT when the valve size and adjoining pipe sizes are identical.
Where,
      Fγ        = Specific Heat Ratio Factor, (γ/1.4)
      xTP      = Combined Pressure Drop Ratio Factor and Piping Geometry Factor
      xT        = Critical Pressure Drop Ratio Factor (retrieved from manufacturer data)

The expansion factor (Y) accounts for the change in density as the fluid flow from the valve inlet to the vena contracta (where the area is the least). The expansion factor shall be calculated using the following equation.

Flashing and Cavitation (Incompressible Service Valve)

The occurrence of flashing and cavitation within a valve can have a significant effect on the valve sizing procedure. Structural damage to the valve and adjacent piping may also result. Knowledge of what is actually happening within the valve might consider the selection of size or style of a valve which can reduce or compensate for the undesirable effect of flashing or cavitation.

To maintain a steady flow of liquid through the valve, the velocity must be greatest at the vena contracta, where cross sectional area is the least. The increase in velocity (or kinetic energy) is accompanied by a substantial decrease in pressure (or potential energy) at the vena contracta. Further downstream, as the fluid stream expands into a larger area, velocity decreases and pressure increases. But of course downstream pressure never recovers completely to equal the pressure that existed upstream of the valve. The differential pressure (ΔP) that exists across the valve is a measure of the amount of energy that was dissipated in the valve. Figure below provides a pressure profile explaining the difference performance between high recovery valve and a valve with lower recovery capabilities due to greater internal turbulence and dissipation of energy.
If pressure at the vena contracta should drop below the vapor pressure of the fluid (due to increased fluid velocity at this point) bubbles will form in the flow stream. Formation of bubbles will increase greatly as vena contracta pressure drops further below the vapor pressure of the liquid. At this stage, there is no difference between flashing and cavitation, but the potential for structural damage to the valve definitely exists.

If pressure at the valve outlet remains below the vapor pressure of the liquid, the bubbles will remain in the downstream system and the process is said to have flashed. On the other hand, if downstream pressure recovery is sufficient to raise the outlet pressure above the vapor pressure of the liquid, the bubbles will collapse, or implode, producing cavitation. Collapsing of the vapor bubbles releases energy and produces a noise similar to what one would expect if gravel were flowing through the valve.

Choked Flow

The phenomenon of choked flow occurs when the normal relationship between flow and increased pressure drop is broken. With choked flow, the mass flowrate will not increase with a further decrease in the downstream pressure while upstream pressure is fixed.

Basic valve sizing equations imply that, flow should continually increase by simply increasing the differential pressure across the valve. In reality, the relationship given by these equations holds true for only a limited range. As the differential pressure is increased, a point is reached where the flow increase stops. This condition of limited maximum flow is known as choked flow.
For compressible flow, the physical point at which the choking flow occurs for adiabatic condition is when the velocity reaches sonic velocity or Mach number of 1. Using the conservation laws of fluid dynamics and thermodynamics, the following relationship is developed.
Where,
      dP       = Differential Pressure          
      ρ         = Mass Density
      v         = Fluid Velocity
      dA       = Differential Cross-Section Area
      M        = Mach Number

The term ρv2/A is always positive, then the value of dP can be positive or negative depends on the dA and Mach Number. The meaning of the sign change for dP and dA is that the pressure and cross-section area can increase or decrease. It can be shown that the critical Mach Number is 1.
If the Mach Number smaller than 1 (subsonic) dP and dA will have the same sign.
If the Mach Number greater than 1 (supersonic) dP and dA will have the opposite sign.
It can be observed that as the flow at subsonic region or Mach Number < 1, a decreasing of velocity by increasing the area results in increasing the pressure, otherwise an increasing of velocity by decreasing the area results in decreasing the pressure.

Meanwhile as the flow at supersonic region or Mach Number > 1, the behavior is opposite to subsonic region. This phenomenon should be prevented in order to increase the pressure drop across the valve. Because beyond the point of sonic velocity (Mach Number 1) at vena contracta, an increase of velocity/flowrate by decreasing the area (valve travel) will not decreasing the outlet pressure, vice versa.
If the fluid is liquid/incompressible, a different type of choked flow occurs when liquid pressure falls below its vapor pressure at vena contracta (beginning of flashing or cavitation condition), then the liquid will partially flash into bubbles or vapor. The vapor bubbles formation at vena contracta cause rapid change in mixture density which become smaller (actual volume increase) and this will prevent the flow from increasing any further.

Flow Characteristic

The flow characteristic of a control valve is the relationship between the flowrate through the valve and the valve travel as the travel is varied from 0 to 100%. Inherent flow characteristic refers to the characteristic observed with a constant pressure drop across the valve. Inherent valve characteristic is an inherent function of the valve flow passage geometry to the valve travel as the pressure drop is held constant.

Many valve design, particularly rotary ball valve, butterfly valve and eccentric plug valve have their own inherent characteristic which cannot be easily changed. However, most globe valves have selection of valve cage or plugs that can be interchanged to modify the inherent flow characteristic. The three most common types of flow characteristics are quick opening, equal percentage and linear as shown in the following figure.
Control system performance is influenced by the gains of each control element (i.e. sensor, transmitter, controller, valve and process) where gain means the slope or ratio of %output to %input. Good system performance means there is minimal overshoot and quick response back to steady state for any load change. In other words, the system can make accurate prediction in short times or trials to changes the manipulated variable to maintain the controlled variable at desired point.
Each control element has its own gain and the product of these gains has a great impact on the stability of the system. The loop gain as shown in Figure 6 is defined by taking the product of all gains.
Since the load does not affect gains of the sensor (GS), transmitter (GT) and controller (GC) it can be assumed that keeping the process gain (GP) and valve gain (GV) constant will ensure stability of the system. So if the process gain is doubled then the valve gain must be cut in half to maintain the GV GP value constant. It can be concluded that selection of valve characteristic or gain is important to maintain the stability of process control for any expected load.

As shown at Figure above, the process gain is illustrated by ratio of the %controlled variable to the %manipulated variable. As example for pressure control valve, the controlled variable is pressure and the manipulated variable is the velocity at vena contracta. Refer to the Bernoulli’s equation it has shown that pressure decrease is proportional to increase in squared velocity (P ≈ 1/v2). As the output of valve gain is %flow/%area then the input of process gain should be the same to connecting between the process gain and valve gain as shown in Figure below.
The figure above illustrated the example of overall gain for process control where the pressure at outlet valve as the controlled variable. The input of valve gain is %travel and the output is %area (%velocity at vena contracta). Meanwhile for process gain, the %area as the input and results %pressure as the output (in this example the valve is assumed with low recovery pressure). It is observed from the process gain at small percentage area (0-20%) results in high pressure difference, because at high velocity causes higher pressure difference than at lower velocity (high percentage area). So it needs valve characteristic that produce small percentage area at low %travel to reaches linearity between %travel (input valve gain) and %pressure (output process gain).

Imagine if the valve characteristic used is linear or quick opening where at low %travel produce higher %area then equal-percentage valve type, It results the overall gain become far away from linear relationship. Which means at low %travel with small change of valve travel will produce high difference %pressure (high sensitivity) and at high %travel with some change of valve travel will only produce low difference %pressure, as result the control system performance will have long response time. So the selection of valve characteristic needs in-depth understanding of the process gain.

That's all I know about control valve, as always I expect for your suggestion and help to improve this post as you see fit. Please leave a comment below and thank you for your time.

Reference
  1. ANSI/ISA-75.01.01-2012. Industrial Process Control Valves – Part 2-1: Flow Capacity Sizing equations for fluid flow under installed conditions. August 2012.
  2. Fisher Controls International Inc. Control Valve Handbook 3rd Edition.
  3. Genick Bar-Meir, Ph. D., Fundamentals of Compressible Fluid Mechanics. May 2007.
  4. Valve Manufacturers Association. Guidelines for Selecting the Proper Valve Characteristic. 2003.

1 comment:

  1. The Gate Valves are Bi-Directional.
    They have Nice Shut-Off Characteristics.
    There Will be Minimal Or No Pressure Loss through the Gate Valve.

    ReplyDelete